WTH-165/G/1P-885 Wind
www.watchfuleyesolutions.com Surge Protective Device for Wind System

Description
In accordance with: IEC 61643-1 - Class I and UL1449 Type 4 Location
Location of use: Gen side wind system
Built-in High Energy GDT: Safely applied to MOV+GDT mode to realize Class I surge protection.
It is paired with model WTH-40/C/R/3P-885 Wind (US120431)

Technical Data
Model WTH-165/G/1P-885 Wind
Ordering Code US120432
Max. continuous operating voltage (Uc) 885V (is paired with US120431)
Dc spark-over voltage at 100 V/s >1700V
Requirement Class to IEC61643-1 Class I
Nominal Discharge Current (In) 3x15kA
Max. Discharge Current (Imax) 3x30kA
Pulsed Current (Iimp) 25kA
Voltage protection level (Up) 3.9kV (MOV+GDT)
Residual voltage (Ures @6kV/3kA) -
Protection Modes L-PE (MOV+GDT)
Protective Element High Energy GDT
Follow Current (If) 100A rms
Response Time (tA) <100ns
Leakage Current (at 75%U1mA) None
Thermal Protection NO
Fault Indication NO
Protection Rating (IP Code) IP 20
Short Circuit Current Ratings (SCCR) 20kA rms
Max. Back-up Fuse None
Surge Life at 3kA (8/20μs) >5000 events
Temperature Range - 40°F to 176°F (-40°C to 80°C)
Relative Humidity 0% to 95% noncondensing
Maximum Operating Altitude 10,000 feet (3000m)
Terminal Cross Section 35mm² (solid) / 25mm² (stranded)
Stripping Length Contacts 0.6inches (15mm)
Terminal Screw Torque Max. 3.5Nm
DIN Rail EN60715 35mm top-hat rail
Dimensions DIN 43880 35.8mm (2TE)
Housing Material Thermoplastic (UL94 V-0)
Housing Design Compact design
Net Weight Per Unit 0.4Lb (180g)
Package Dimension (W×H×D) 1.4"×3.6"×2.6" (35.8mm×90mm×66.5mm)
Remote Contacts NO
Contact Ratings 125VAC/3A, 250VAC/1.5A
Terminal Cross Section Max. 1.5mm²
Stripping Length Contacts 0.25inches (6-7mm)
Remote Terminal Torque 0.25Nm

Connection Diagram
Dimensions
Visit us at