| Model |
WTH-165/G/1P-885 Wind |
| Ordering Code |
US120432 |
| Max. continuous operating voltage (Uc) |
885V (is paired with US120431) |
| Dc spark-over voltage at 100 V/s |
>1700V |
| Requirement Class to IEC61643-1 |
Class I |
| Nominal Discharge Current (In) |
3x15kA |
| Max. Discharge Current (Imax) |
3x30kA |
| Pulsed Current (Iimp) |
25kA |
| Voltage protection level (Up) |
3.9kV (MOV+GDT) |
| Residual voltage (Ures @6kV/3kA) |
- |
| Protection Modes |
L-PE (MOV+GDT) |
| Protective Element |
High Energy GDT |
| Follow Current (If) |
100A rms |
| Response Time (tA) |
<100ns |
| Leakage Current (at 75%U1mA) |
None |
| Thermal Protection |
NO |
| Fault Indication |
NO |
| Protection Rating (IP Code) |
IP 20 |
| Short Circuit Current Ratings (SCCR) |
20kA rms |
| Max. Back-up Fuse |
None |
| Surge Life at 3kA (8/20μs) |
>5000 events |
| Temperature Range |
- 40°F to 176°F (-40°C to 80°C) |
| Relative Humidity |
0% to 95% noncondensing |
| Maximum Operating Altitude |
10,000 feet (3000m) |
| Terminal Cross Section |
35mm² (solid) / 25mm² (stranded) |
| Stripping Length Contacts |
0.6inches (15mm) |
| Terminal Screw Torque |
Max. 3.5Nm |
| DIN Rail EN60715 |
35mm top-hat rail |
| Dimensions DIN 43880 |
35.8mm (2TE) |
| Housing Material |
Thermoplastic (UL94 V-0) |
| Housing Design |
Compact design |
| Net Weight Per Unit |
0.4Lb (180g) |
| Package Dimension (W×H×D) |
1.4"×3.6"×2.6" (35.8mm×90mm×66.5mm) |
| Remote Contacts |
NO |
| Contact Ratings |
125VAC/3A, 250VAC/1.5A |
| Terminal Cross Section |
Max. 1.5mm² |
| Stripping Length Contacts |
0.25inches (6-7mm) |
| Remote Terminal Torque |
0.25Nm |