Requirement Class to IEC61643-1 |
Class I+II |
IEEE Category Rating |
C, B & A |
Protection Modes |
L-N |
N-PE |
Nominal Discharge Current (In @8/20μs) |
40kA |
50kA |
Max. Discharge Current (Imax @8/20μs) |
80kA |
100kA |
Pulsed Current (Iimp @10/350μs) |
10kA |
12.5kA |
Protective Element |
MOV |
GDT |
Follow Current (If) |
NO |
100Arms |
Response Time (tA) |
<5ns |
<100ns |
Leakage Current (at 75%U1mA) |
<20μA |
None |
Thermal Protection |
YES |
NO |
Protection Rating (IP Code) |
IP 65 |
Internal Back-up Fuse |
32A |
Short Circuit Current Ratings (SCCR) |
20kA rms |
Surge Life at 3kA (8/20μs) |
>5000 events |
Temperature Range |
- 40°F to 176°F (-40°C to 80°C) |
Relative Humidity |
0% to 95% noncondensing |
Maximum Operating Altitude |
10,000 feet (3000m) |
Terminal Cross Section |
16mm² (solid) / 10mm² (stranded) |
Stripping Length Contacts |
0.6inches (15mm) |
Terminal Screw Torque |
Max. 2Nm |
Housing |
Box Design |
Net Weight Per Unit |
5.86Lb (2.66kg) |
Package Dimension (W×H×D) |
12.2"×7.2"×4.77" (310mm×183mm×121mm) |
Lightning Counter |
LCD with 12 digits (Press ”reset” cleared to “0”) |
Remote Contacts |
YES |
Contact Ratings |
125VAC/3A, 250VAC/1.5A |
Terminal Cross Section |
Max. 1.5mm² |
Stripping Length Contacts |
0.25inches (6-7mm) |
Remote Terminal Torque |
0.25Nm |
The Electricity-getting Mode of Control Panels: L1-L2 (220~480V) |