www.watchfuleyesolutions.com - Menu - Back to TOP -

Paperless Datasheet
Going green and protecting environment is manufacturers' responsibility. Each WatchfulEyE product has a link of downloading data sheet on its enclosure:
http://datasheet.watchfuleyesolutions.com/US120267x4.html

3D file download
http://www.watchfuleyesolutions.com/wth_rar/3D/WTH-100B+CR1P.STEP.zip

Model & Ordering Code

Model Ordering Code MCOV/Uc Remote Contacts UPC/EAN Code
WTH-100/B+C/R/1P-275 US120274 275VAC YES (0) 811914030782
WTH-100/B+C/1P-275 US120264 NO (0) 811914030843
WTH-100/B+C/R/1P-320 US120275 320VAC YES (0) 811914030799
WTH-100/B+C/1P-320 US120265 NO (0) 811914030850
WTH-100/B+C/R/1P-385 US120276 385VAC YES (0) 811914030805
WTH-100/B+C/1P-385 US120266 NO (0) 811914030867
WTH-100/B+C/R/1P-420 US120277 420VAC YES (0) 811914030812
WTH-100/B+C/1P-420 US120267 NO (0) 811914030874



Certificates of Products

www.watchfuleyesolutions.com - Page 01 - Back to TOP -

More Package
Model with suffix WTH-100/B+C/R/1P-275 x2pcs x3pcs x4pcs
Ordering Code US120274 US120274x2 US120274x3 US120274x4
Model with suffix WTH-100/B+C/1P-275 x2pcs x3pcs x4pcs
Ordering Code US120264 US120264x2 US120264x3 US120264x4
Model with suffix WTH-100/B+C/R/1P-320 x2pcs x3pcs x4pcs
Ordering Code US120275 US120275x2 US120275x3 US120275x4
Model with suffix WTH-100/B+C/1P-320 x2pcs x3pcs x4pcs
Ordering Code US120265 US120265x2 US120265x3 US120265x4
Model with suffix WTH-100/B+C/R/1P-385 x2pcs x3pcs x4pcs
Ordering Code US120276 US120276x2 US120276x3 US120276x4
Model with suffix WTH-100/B+C/1P-385 x2pcs x3pcs x4pcs
Ordering Code US120266 US120266x2 US120266x3 US120266x4
Model with suffix WTH-100/B+C/R/1P-420 x2pcs x3pcs x4pcs
Ordering Code US120277 US120277x2 US120277x3 US120277x4
Model with suffix WTH-100/B+C/1P-420 x2pcs x3pcs x4pcs
Ordering Code US120267 US120267x2 US120267x3 US120267x4

www.watchfuleyesolutions.com - Page 02 - Back to TOP -

Description
In accordance with: IEC/EN61643-11 - Class I+II and UL1449 Type 4 Location
Location of use: main sub-distribution boards, branch sub-distribution boards
Plug-in module and separate base design enables convenient maintenance.
Internal thermal disconnect devices help ensure safe or at end-of-life
WTH-100/B+C/R/1P Series Technical Data
Requirement Class to IEC/EN61643-11 Class I+II
IEEE Category Rating C, B & A
Nominal Discharge Current (In) 50kA
Max. Discharge Current (Imax) 100kA
Pulsed Current (Iimp) 12.5kA
Protection Modes L-PE, N-PE
Protective Element High Energy MOV
Follow Current (If) NO
Response Time (tA) <5ns
Leakage Current (at 75%U1mA) <20μA
Thermal Protection YES
Protection Rating (IP Code) IP 20
Short Circuit Current Ratings (SCCR) 25kA rms
Max. Back-up Fuse (if mains >100A) 100A gL (circuit-breaker: <50A)
Surge Life at 3kA (8/20μs) >5000 events
Temperature Range - 40°F to 176°F (-40°C to 80°C)
Relative Humidity 0% to 95% noncondensing
Maximum Operating Altitude 10,000 feet (3000m)
Terminal Cross Section 35mm² (solid) / 25mm² (stranded)
Stripping Length Contacts 0.6inches (15mm)
Terminal Screw Torque Max. 3.5Nm
DIN Rail EN60715 35mm top-hat rail
Dimensions DIN 43880 36mm (2TE)
Housing Material Thermoplastic (UL94 V-0)
Housing Design Modular design
Net Weight Per Unit 0.5Lb (227g)

www.watchfuleyesolutions.com - Page 03 - Back to TOP -
.

Surge Protection Connection Diagram


Indication of two levels of surge protection
The capability of displaying 50 percent of surge protection capacity: under normal circumstances, with two MOVs' protection at the same time, the module can realize Class I surge protection; in case that one of the indicator windows indicates red, there's still 50% of surge protection capacity to meet Class II surge protection requirements, and the module shall be replaced timely at this point.

Maximum Continuous Operating Voltage (MCOV/Uc) 275VAC 320VAC 385VAC 420VAC
Voltage Protection Level (Up) 1.9kV 2.1kV 2.2kV 2.3kV
Residual Voltage (Ures) 1.0kV 1.1kV 1.2kV 1.4kV


Dimensions


www.watchfuleyesolutions.com - Page 04 - Back to TOP -
.

Remote Contacts (Dry Contacts)
1: COM (Common)
2: NC (Normally Close)
3: NO (Normally Open)


Contact Ratings 125VAC/3A, 250VAC/1.5A
Terminal Cross Section Max. 1.5mm²
Stripping Length Contacts 0.25 inches (6-7mm)
Remote Terminal Torque 0.25Nm


Fault Indication

www.watchfuleyesolutions.com - Page 05 - Back to TOP -

Common Terms and Definitions
1. Normal operating voltage rating (Un)
2. Maximum Continuous Operating Voltage (Uc/MCOV):
Maximum r.m.s. voltage, which may be continuously applied to the surge protective device's mode of protection.
3. Nominal Discharge Current for Class II Test (In):
crest value of the current through the surge protective device having a current waveshape of 8/20μs.
4. Maximum Discharge Current (Imax):
Crest value of a current through the surge protective device having an 8/20μs waveshape and magnitude according to the manufacturers specification. Imax is equal to or greater than In.
5. Voltage Protection Level (Up):
Maximum voltage to be expected at the surge protective device terminals due to an impulse stress with defined voltage steepness and an impulse stress with a discharge current with given amplitude and waveshape.
6. Residual Voltage (Ures):
Crest value of voltage that appears between the terminals of an surge protective device due to the passage of discharge current.
7. IEEE 62.41
CATEGORY C: outdoor overhead lines, service entrance (most severe)
CATEGORY B: major feeder, short branch circuits, service panel (indoor)
CATEGORY A: long branch circuits, receptacles (indoor) (least severe)

How to choose a suitable Uc(MCOV) value
Note: Uc >1.15Un
The relationship between two parameters Uc and Up of a surge protective device is proportional.
If Uc is small, the value of Up is also small; surge protective devices with smaller Up can provide better surge protection.
Whether to choose smaller Uc depends on the voltage stability of the grid.
If you choose surge protective devices with smaller Uc for the grid with instable voltage, the surge protective devices will frequently work while the grid voltage fluctuates, resulting in shortening surge protective device's product life.
If you choose larger Uc, and the value of Up is accordingly large, the surge protective efficiency will not be so fine.
If you are unsure of the voltage stability of the grid,
it is suggested to calculate MCOV(Uc) using the following formula: √ 2  Un < Uc < √ 3 Un

AC Network (Un) MCOV(Uc), L/N-PE Protection Mode
110V, 120/208V, 127/220V 150V
220/380V 275V, 320V, 385V
230/400V 275V, 320V, 385V, 420V
240/415V 320V, 385V, 420V
266/460V, 277/480V 385V, 420V
347/600V 550V, 690V
Wind Power System 690V (Grid side ), 885V (Gen side )

www.watchfuleyesolutions.com - Page 06 - Back to TOP -
.

AC Network Connection Diagram (1/2)





www.watchfuleyesolutions.com - Page 07 - Back to TOP -
.

AC Network Connection Diagram (2/2)


Difference mode & Common mode Connection Diagram


Common mode:L-PE, N-PE surge protection
Difference mode:L-N surge protection

www.watchfuleyesolutions.com - Page 08 - Back to TOP -
.

Selection of back-up fuse

Selection of back-up circuit-breaker

www.watchfuleyesolutions.com - Page 09 - Back to TOP -
.

Application


Key
1. Origin of the installation
2. Distribution board
3. Distribution outlet
4. Main earthing terminal or bar
5. Surge protective device, class I or II tested
6. Earthing connection (earthing conductor) of the surge protective device
7. Fixed equipment to be protected
8. Surge protective device, class II tested
9. Surge protective device, class II or class III tested
10. Decoupling element or line length
F1, F2, F3 overcurrent protective disconnectors
NOTE Refer to IEC 61643-12 for further information.

www.watchfuleyesolutions.com - Page 10 - Back to TOP -

N-PE Module
WTH-100/G module integrates High-Energy GDT, no leakage current. It pairs WTH-100/B+C/R series surge protector, combined into N-PE protection mode, the two modules are the same in dimension and shape, and are connected with a dedicated bus-bar to achieve a perfect combination.
WTH-100/G Technical Data
Max. continuous operating voltage (Uc) 255V
Nominal Discharge Current (In) 50kA
Max. Discharge Current (Imax) 100kA
Pulsed Current (Iimp) 37.5kA
Voltage protection level (Up) 1.2kV
Protection Modes N-PE only
Protective Element High Energy GDT
Follow Current (If) 100A rms
Response Time (tA) <100ns
Net Weight Per Unit 0.4Lb (180g)

3P + NPE Combintion Package
Model with suffix Ordering Code Model with suffix Ordering Code
WTH-100/B+C/R/1P-275 x3pcs +NPE US120274x3N WTH-100/B+C/1P-275 x3pcs +NPE US120264x3N
WTH-100/B+C/R/1P-320 x3pcs +NPE US120275x3N WTH-100/B+C/1P-320 x3pcs +NPE US120265x3N
WTH-100/B+C/R/1P-385 x3pcs +NPE US120276x3N WTH-100/B+C/1P-385 x3pcs +NPE US120266x3N
WTH-100/B+C/R/1P-420 x3pcs +NPE US120277x3N WTH-100/B+C/1P-420 x3pcs +NPE US120267x3N


1P + NPE Combintion Package
Model with suffix Ordering Code Model with suffix Ordering Code
WTH-100/B+C/R/1P-275 +NPE US120274x1N WTH-100/B+C/1P-275 +NPE US120264x1N
WTH-100/B+C/R/1P-320 +NPE US120275x1N WTH-100/B+C/1P-320 +NPE US120265x1N
WTH-100/B+C/R/1P-385 +NPE US120276x1N WTH-100/B+C/1P-385 +NPE US120266x1N
WTH-100/B+C/R/1P-420 +NPE US120277x1N WTH-100/B+C/1P-420 +NPE US120267x1N

www.watchfuleyesolutions.com - Page 11 - Back to TOP -

FAQ & Help
1. What should I do if I can't find the paper manual in the product packaging?
Watchful Eye products is committed to going green with paperless data sheets. On the side of each product enclosure is an engraved link with URL for downloading paperless data sheet and QR code of the website. If you need the paper data sheet, you can open the link and print the data sheet by yourself.

2. The advantages of fault indication windows?
If surge protection fails, the fault indication windows will turn red, thus it can be seen intuitively, and the surge protective device can be replaced in time to avoid damage to the equipment caused by a second surge.

3. What instruments can be used to test whether its surge protection function is normal or not?
Test with a Watchful Eye surge protector tester

4. Can you list more applications?
Power supply panel, whole house

5. What is the feature of Class I+II?
It provides high capability of Class I surge protection, and capability of Class II (equivalent to the parameters of WTH-40 ) fine protection with low residual voltage as well, applying to Class I and Class II surge protection in multiple areas. If you are not sure which module to choose for protecting your area, Class I + II is the best solution.


www.watchfuleyesolutions.com - Page 12 - Back to TOP -

Download WatchfulEyE Official App
To learn about more products and updates from company, please scan QR code to download the official App:

After-sale Services
Watchful Eye provides a 5-year quality warranty globally.


I have a question

www.watchfuleyesolutions.com - Page 13 - Back to TOP -