WTH-120/B/...115 Series
www.watchfuleyesolutions.com Surge Protective Device for AC Power Supply System

Paperless Datasheet
Going green and protecting environment is manufacturers' responsibility. WatchfulEye products have the links of downloading data sheet on its enclosure:
http://datasheet.watchfuleyesolutions.com/US120292.html

Description
In accordance with: IEC 61643-1 - Class I and UL1449 Type 4 Location
Location of use: main sub-distribution boards
With three MOVs' protection at the same time, the module can realize Class I surge protection; in case that two of the indicator windows indicates red, it can still meet
Class II surge protection requirements.

Ordering Information
Model Ordering code
WTH-120/B/1P-115 US120292
WTH-120/B/1P-115 x2pcs US120292x2
WTH-120/B/1P-115 x3pcs US120292x3
WTH-120/B/1P-115 x4pcs US120292x4

Technical Data
Model WTH-120/B/1P-115
Requirement Class to IEC61643-1 Class I
IEEE Category Rating C & B
Max. continuous operating voltage (Uc) 115VAC 50/60Hz
Voltage protection level (Up) 1.7kV
Residual voltage (Ures @6kV/3kA) 0.7kV
Nominal Discharge Current (In) 60kA
Max. Discharge Current (Imax) 120kA
Pulsed Current (Iimp) 15kA
Protection Modes L-PE, N-PE
Protective Element High Energy MOV
Follow Current (If) NO
Response Time (tA) <5ns
Leakage Current (at 75%U1mA) <20μA
Thermal Protection YES
Protection Rating (IP Code) IP 20
Short Circuit Current Ratings (SCCR) 25kA rms
Max. Back-up Fuse (if mains >160A) 160A gL (circuit-breaker: <100A)
Surge Life at 3kA (8/20μs) >5000 events
Temperature Range - 40°F to 176°F (-40°C to 80°C)
Relative Humidity 0% to 95% noncondensing
Maximum Operating Altitude 10,000 feet (3000m)
Terminal Cross Section 35mm² (solid) / 25mm² (stranded)
Stripping Length Contacts 0.6inches (15mm)
Terminal Screw Torque Max. 3.5Nm
DIN Rail EN60715 35mm top-hat rail
Dimensions DIN 43880 35.8mm (2TE)
Housing Material Thermoplastic (UL94 V-0)
Housing Design Compact design
Net Weight Per Unit 0.46Lb (209g)
Package Dimension (W×H×D) 1.4"×3.6"×2.6" (35.8mm×90mm×66.5mm)
Remote Contacts NO
Contact Ratings 125VAC/3A, 250VAC/1.5A
Terminal Cross Section Max. 1.5mm²
Stripping Length Contacts 0.25inches (6-7mm)
Remote Terminal Torque 0.25Nm

Connection Diagram
Dimensions
Fault Indication
Visit us at